More products

More products

UL Type RHW-2 Double Insulated Wire

Rated temperature : -40 ~ 90°C

Rated voltage : 2000V

Passes UL VW-1 vertical flame test

Specifications

  • Conductor : Stranded Tinned Copper

  • Insulation : XLPE

  • Jacket : XLPE

  • Rated temperature : -40 ~ 90°C

  • Rated voltage : 2000V

  • Reference standard : UL 44, UL 2556

  • Passes UL VW-1 vertical flame test

  • Cold bend test : -40 ± 2°C x 4hrs (No crack)

  • Deformation : 131 ± 2°C x 30mins (<30%)


ConductorInsulationJacketMax. Allowable Ampacity*Max. DC Resistance
at 20°C
(ohm/km)
AWGNo./mmDiameter
(mm)
Thickness
(mm)
Diameter
(mm)
Thickness
(mm)
Diameter
(mm)
65°C70°C90°C
1449/0.252.021.525.600.386.601515158.78
1265/0.2542.361.525.800.386.802020205.53
10105/0.2543.001.526.500.768.103030303.48
8169/0.2543.811.787.800.769.504050552.16
619/55/0.1275.201.789.200.7611.005565751.36
419/37/0.206.701.7810.700.7612.507085950.856
219/35/0.2548.651.7812.801.1415.10951151300.538
119/44/0.2549.702.2914.801.1417.201101301500.427
1/019/55/0.25410.852.2916.001.1418.501251501700.337
2/019/70/0.25412.252.2917.501.1420.001451751950.267
3/019/88/0.25413.752.2919.001.1421.501652002250.212
4/019/78/0.3215.802.2920.901.6524.501952302600.168

* The values of allowable ampacity is shown according to NEC, and is subject to the final specification.